MMC-16 APC to 2 x MTP-8 UPC Breakout Cable, 16 Fibers, OM4
MMC-16 APC to 2 x MTP-8 UPC Breakout Cable, 16 Fibers, OM4

For UAE project teams, the key is to match this exact configuration to the port schedule, optical budget and delivery documentation. The 16FMMCMTPOM4 APC-to-UPC breakout divides sixteen OM4 fibers from one MMC APC female connector into two MTP-8 UPC female branches. It is built for multimode channels that require this precise polish combination. The direct fan-out replaces cassette-based conversion with one factory-tested unit and two unambiguously identifiable eight-fiber routes.

Product Highlights

  • MMC Female to MTP® Female, 16 Fibers
  • OM4 50/125μm, bend-insensitive fiber
  • MMC insertion loss ≤0.35dB, return loss ≥40/27dB (MMC/MTP®)
  • Harness Polarity wiring scheme
  • 2.5mm Plenum (OFNP) cable
  • Standard length options: 1m (3ft), 2m (7ft), 3m (10ft)

Specifications

Part Number16FMMCMTPOM4
ManufacturerHT
Connector AUS Conec MMC Female (Non-Pinned)
Connector BUS Conec MTP® Elite Female (Non-Pinned)
Polish TypeAPC to UPC
Glass FiberBend Insensitive Fiber
Fiber ModeOM4 50/125μm
Wavelength850/1300nm
Fiber Count16 Fibers
PolarityHarness Polarity
Cable Outside Diameter (OD)2.5mm
Cable JacketPlenum (OFNP)
Min. Bend Radius (Optical Fiber)7.5mm
Min. Bend Radius (Fiber Cable)20/10D (Dynamic/Static)
Tensile Strength (Long Term)30N
Tensile Strength (Short Term)100N
Insertion Loss≤0.35dB
Return Loss≥40/27dB (MMC/MTP®)
Attenuation at 850nm≤2.3dB/km
Attenuation at 1300nm≤0.6dB/km
Operating Temperature-10 to 60°C (14 to 140℉)
Storage Temperature-10 to 70°C (14 to 158℉)

A mixed-polish multimode fan-out

APC at the MMC side and UPC at the two MTP ends must be matched to the surrounding interfaces; this version ought to not be substituted for the APC-to-APC breakout. The female, non-pinned connectors require pinned mates. Because the two MTP branches may serve distinct destination ports, label every branch and record its map before dressing this cable into a manager.

Reflection and insertion-loss values by connector

Maximum insertion loss is 0.35dB. Return loss is specified individually as at least 40dB for the MMC APC interface and 27dB for the MTP UPC interface. Those figures should be retained in acceptance documentation rather than replaced by a single general-purpose figure. OM4 fiber supports the 850/1300nm multimode link, while reach remains determined by the chosen transceivers.

Installing the two-leg assembly

The standard total lengths are 1m (3ft), 2m (7ft) and 3m (10ft); customized meter and foot lengths are offered. Location this fan-out so neither MTP leg is pulled sideways, and respect the 7.5mm optical-fiber bend radius. Clean and examine the MMC and the two MTP ferrules before making the three connections.

Ordering and Factory Support

State 16FMMCMTPOM4 in the APC-to-UPC two-branch model, with length and unit count. For repeat installations, customized branch IDs and a customer part-number label may keep these mixed-polish cables distinct from the APC-to-APC variants. Our UAE project support can review the requirement with Shenzhen production before a formal quotation is issued.

 

Fiber Optic UAE supplies MMC-16 APC to 2 x MTP-8 UPC Breakout Cable, 16 Fibers, OM4 to data centers, ISPs and enterprises in Dubai, Abu Dhabi, Sharjah and across the Gulf region, with project support from our UAE office and production coordination from our Shenzhen factory.


UAE Fiber Optics

UAE office: Abu Dhabi,Al khaleej Al Arabi
Factory add: ZYT industrial area, Shiyan, Baoan district, Shenzhen, China 518000

Popular Products

  • Fiber Optic Patch Cord
  • Fiber Optic Pigtail
  • Fiber Optic Attenuator
  • Fiber Optic Patch Panel
  • Fiber Optic Adapter

Products Datasheet

PDF catalogues of our products to download or for general inquiry, please send an email to sales@huihongfiber.com for details.

Customer Support

For customer support, please leave email to sales@huihongfiber.com, we shall reply to you as soon as possible.