MMC-16 APC to 8 x LC UPC Harness Cable, 16 Fibers, OM4
MMC-16 APC to 8 x LC UPC Harness Cable, 16 Fibers, OM4

For UAE project teams, the key is to match this exact configuration to the port schedule, optical budget and delivery documentation. This OM4 MMC-to-LC harness fans one MMC-16 APC female connector out to eight LC UPC duplex legs. Sixteen bend-insensitive multimode fibers offer eight duplex routes for switches, servers or patch panels. The single 2.5mm plenum trunk keeps the primary path compact, while factory-built LC branches eliminate the need for a distinct multimode cassette.

Product Highlights

  • MMC Female to LC UPC Duplex, 16 Fibers
  • OM4 50/125μm, bend-insensitive fiber
  • MMC insertion loss ≤0.35dB, return loss ≥40dB
  • LC insertion loss ≤0.2dB, return loss ≥30dB
  • Harness Polarity wiring scheme
  • 2.5mm Plenum (OFNP) cable
  • Standard length options: 1m (3ft), 2m (7ft), 3m (10ft)

Specifications

Part Number16FMMCLCOM4
ManufacturerHT
Connector AUS Conec MMC Female (Non-Pinned)
Connector BLC UPC Duplex
Polish TypeAPC to UPC
Glass FiberBend Insensitive Fiber
Fiber ModeOM4 50/125μm
Wavelength850/1300nm
Fiber Count16 Fibers
PolarityHarness Polarity
Cable Outside Diameter (OD)2.5mm
Cable JacketPlenum (OFNP)
Min. Bend Radius (Optical Fiber)7.5mm
Min. Bend Radius (Fiber Cable)20/10D (Dynamic/Static)
Tensile Strength (Long Term)30N
Tensile Strength (Short Term)100N
MMC Connector IL≤0.35dB
MMC Connector RL≥40dB
LC Connector IL≤0.2dB
LC Connector RL≥30dB
Attenuation at 850nm≤2.3dB/km
Attenuation at 1300nm≤0.6dB/km
Operating Temperature-10 to 60°C (14 to 140℉)
Storage Temperature-10 to 70°C (14 to 158℉)

Direct fan-out for multimode equipment

This harness is suitable when a MMC-based parallel interface must connect to LC duplex hardware using OM4. It does not perform electronic conversion or change lane speeds; it offers the passive fiber mapping only. Verify that the active port expects this breakout arrangement and that each LC leg is assigned to the proper duplex destination.

MMC and LC optical values

Maximum insertion loss is 0.35dB at MMC and 0.2dB at LC. Minimum return loss is 40dB for the MMC APC interface and 30dB for LC UPC. OM4 attenuation is 2.3dB/km at 850nm and 0.6dB/km at 1300nm. Use these figures with the transceiver budget and other connections to evaluate every entire duplex connection.

Managing eight LC duplex branches

Select standard length options of 1m (3ft), 2m (7ft) or 3m (10ft), or specify customized meter and foot lengths. Eight branch pairs need orderly routing to prevent crossed transmit and receive connections. Label the legs before bundling, support this fan-out body and maintain the 7.5mm minimum fiber bend radius near these connectors.

Ordering and Factory Support

Reference 16FMMCLCOM4 with the necessary length and unit count. Provide your preferred LC branch identifiers and MMC label particulars; the factory may align these markings with the rack’s duplex-port numbering to simplify future moves and fault finding. Our UAE project support can review the requirement with Shenzhen production before a formal quotation is issued.

 

Fiber Optic UAE supplies MMC-16 APC to 8 x LC UPC Harness Cable, 16 Fibers, OM4 to data centers, ISPs and enterprises in Dubai, Abu Dhabi, Sharjah and across the Gulf region, with project support from our UAE office and production coordination from our Shenzhen factory.


UAE Fiber Optics

UAE office: Abu Dhabi,Al khaleej Al Arabi
Factory add: ZYT industrial area, Shiyan, Baoan district, Shenzhen, China 518000

Popular Products

  • Fiber Optic Patch Cord
  • Fiber Optic Pigtail
  • Fiber Optic Attenuator
  • Fiber Optic Patch Panel
  • Fiber Optic Adapter

Products Datasheet

PDF catalogues of our products to download or for general inquiry, please send an email to sales@huihongfiber.com for details.

Customer Support

For customer support, please leave email to sales@huihongfiber.com, we shall reply to you as soon as possible.