MMC-24 APC to MTP-24 UPC Jumper, 24 Fibers, OM4
MMC-24 APC to MTP-24 UPC Jumper, 24 Fibers, OM4

For UAE project teams, the key is to match this exact configuration to the port schedule, optical budget and delivery documentation. The 24FMMCMTPOM4 jumper combines a 24-fiber MMC APC female interface with a 24-fiber MTP UPC female interface. This mixed-polish OM4 unit is intended for channels that specifically require APC at the MMC side and UPC at the MTP side. It is not interchangeable with the APC-to-APC model, even though the two products share the identical fiber count and connector families.

Product Highlights

  • MMC Female to MTP® Female, 24 Fibers
  • OM4 50/125μm, bend-insensitive fiber
  • MMC insertion loss ≤0.35dB, return loss ≥40/20dB (MMC/MTP®)
  • Jumper Polarity wiring scheme
  • 2.5mm Plenum (OFNP) cable
  • Standard length options: 1m (3ft), 2m (7ft), 3m (10ft)

Specifications

Part Number24FMMCMTPOM4
ManufacturerHT
Connector AUS Conec MMC Female (Non-Pinned)
Connector BUS Conec MTP® Elite Female (Non-Pinned)
Polish TypeAPC to UPC
Glass FiberBend Insensitive Fiber
Fiber ModeOM4 50/125μm
Wavelength850/1300nm
Fiber Count24 Fibers
PolarityJumper Polarity
Cable Outside Diameter (OD)2.5mm
Cable JacketPlenum (OFNP)
Min. Bend Radius (Optical Fiber)7.5mm
Min. Bend Radius (Fiber Cable)20/10D (Dynamic/Static)
Tensile Strength (Long Term)30N
Tensile Strength (Short Term)100N
Insertion Loss≤0.35dB
Return Loss≥40/20dB (MMC/MTP®)
Attenuation at 850nm≤2.3dB/km
Attenuation at 1300nm≤0.6dB/km
Operating Temperature-10 to 60°C (14 to 140℉)
Storage Temperature-10 to 70°C (14 to 158℉)

Why the polish combination matters

APC and UPC end faces have distinct geometry and reflection behavior. They ought to never be forced jointly in a mating adapter. Because this jumper deliberately places APC on the MMC connector and UPC on the MTP Elite connector, the surrounding link must present the matching APC and UPC interfaces. Checking the polish at every end is as important as confirming 24-fiber compatibility.

Twenty-four fibers in a compact route

One 2.5mm OFNP jumper carries all 24 fibers, reducing cable bulk compared with twelve duplex patch cords. The two connectors are female and non-pinned, and factory jumper polarity controls the internal mapping. The MMC side offers at least 40dB return loss; the UPC MTP side is rated at 20dB minimum, with 0.35dB maximum insertion loss for this assembly.

Ordering and installing the correct version

Standard choices are 1m (3ft), 2m (7ft) and 3m (10ft), plus made-to-order lengths in feet or meters. Specify this APC-to-UPC version unambiguously in rack documentation to distinguish it from APC-to-APC patch cords. While installing, examine the ferrules, observe the key orientation and maintain the 7.5mm minimum optical-fiber bend radius around the MMC and MTP boots.

Ordering and Factory Support

Reference 24FMMCMTPOM4 and explicitly verify the APC-to-UPC need, length and unit count. A simple port plan showing the MMC and MTP mating interfaces will help prevent an accidental substitution with the APC-to-APC version. Our UAE project support can review the requirement with Shenzhen production before a formal quotation is issued.

 

Fiber Optic UAE supplies MMC-24 APC to MTP-24 UPC Jumper, 24 Fibers, OM4 to data centers, ISPs and enterprises in Dubai, Abu Dhabi, Sharjah and across the Gulf region, with project support from our UAE office and production coordination from our Shenzhen factory.


UAE Fiber Optics

UAE office: Abu Dhabi,Al khaleej Al Arabi
Factory add: ZYT industrial area, Shiyan, Baoan district, Shenzhen, China 518000

Popular Products

  • Fiber Optic Patch Cord
  • Fiber Optic Pigtail
  • Fiber Optic Attenuator
  • Fiber Optic Patch Panel
  • Fiber Optic Adapter

Products Datasheet

PDF catalogues of our products to download or for general inquiry, please send an email to sales@huihongfiber.com for details.

Customer Support

For customer support, please leave email to sales@huihongfiber.com, we shall reply to you as soon as possible.